News
- 2011-12-19 19:00:23
-
Kb0 which cooked participation and description:
KB0-12C / M0.25 / 06MF, KB0-12C / M0.4 / 06MF, KB0-12C / M0.63 / 06MF, KB0-12C / M1 / 06MF, KB0-12C / M1.6 / 06MF, KB0-12C / M2.5 / 06MF, KB0-12C / M4 / 06MF, KB0-12C / M6.3 / 06MF, KB0-12C / M12 / 06MF, KB0-16C / M16 / 06MF, KB0-18C / M18 / 06MF, KB0-32C / M25 / 06MF, KB0-32C / M32 / 06MF, KB0-45C / M40 / 06MF, KB0-45C / M45 / 06MF, KB0-63C / M50 / 06MF, KB0-63C / M63 / 06MF, KB0-100C / M80 / 06MF, KB0-100C / M100 / 06MF, KB0-125C / M125 / 06MF
12, 16, 18, 32, 45, 63100125: the frame body rated current
C, Y, H: C breaking capacity for 35KA (economy), Y breaking capacity for 50KA ( standard), H breaking capacity for 80KA ( high breaking type)
M: release code
0.16-125: rated current
06 ( 02): attachment assembly code
M: control of power supply for M 220V.Q 380V representative representative
F, G: F derived symbol, on behalf of the fire type only alarm non-tripping, G represents the main circuit isolation function
CPS" control and protection switch in low voltage electric apparatus" is a new product, as new categories of products, its product category for" CPS"," Control and Protective Switching is the English abbreviation of Device".
CPS ( IKB0 ) meet standards: IEC60947 - 6 - 2: ( 2002)" low voltage switchgear and controlgear - Part sixth multi function electrical section second control and protective switching devices" and GB14048.9 - 1998" low voltage switchgear and controlgear multiple function equipment: control and protective switching devices ( equivalent to" by IEC60947 - 6 - 2 ).
The large instantaneous short-circuit protection: protection current and rated current of the switch main body, its current setting for the 20In + 20%, T4 = 2 ~ 3MS action time.
The instantaneous short-circuit protection: current protection and electronic breaker rated current, the current setting for 16In - 15%, T3 < 0.1ms action time.
The short circuit short-time delay or fixed protection: current protection and electronic breaker rated current, the current setting panel adjustable ( 6 ~ 12Ir1 ) + 15% ( for motor protection), ( 3 ~ 6Ir1 ) + 10% ( power distribution protection ), delay action setting time T2 = 0.2S
The long-time delay overload protection: current protection and electronic breaker rated current, the current setting of Ir1 panel adjustable 0.4 ~ 1Ie, inverse time characteristic for I2T = ( 1.5Ir1 ) 2t1, T1 for long time delay current 1.5Ir1 setting time, distribution by T1 = 64S, T1 = 128s motor
The lack of phase, phase failure protection: action setting time for 2S
The three-phase unbalance protection: arbitrary phase current difference of more than 50%, action setting time for 2S
The overvoltage protection: phase 470 + 10V, 5S action setting time
The undervoltage protection: phase 270 + 10V, 5S action setting time
The start-up delay: short circuit short-time delay or time limit does not protect, setting time for 2S
The fire interface: DC 24V fire interface output ( optional)
The residual current leakage protection: customized according to customer requirements, the action time of 0.1s ( time delay for 0.3s ) ( optional)
The warning function: current adjustable
The online programming function
The fault indicator
The above description information by the country electric switch factory offers, www.jiandq.com
- Previous [Return Home] [Print] [Go Back] Next
Brand Zone
Products Search